What is Parallel Operation of Generator?
• Parallel Operation of Generator Means to
connect one generator to another live generator
or grid (infinite bus bar) for sharing load.
• The live generator is called running generator
and others is called incoming generator.
• Parallel operation of generator
need synchronization.
Generator 1 - Running Generator
Generator 2 - Incoming Generator
Why Parallel operation of Generator?
• Continuity of Supply and Maintenance
(Redundancy and serviceability)
• Efficiency
• Expansion Plans (Expandability)
• Size of Alternators
• Maximize Power System Reliability:
AC Generator
Voltage Induced in a Single Phase Generator
Voltage induced In a Three Phase Generator
Condition of Synchronizing
• Voltage of all generators must be equal.
• Voltage phase angle of all generators must be
equal.
• Phase sequence/ ratation of all generators must
be equal.
• Frequency (no load frequency) of the incoming
must be slightly greater than the frequency (no
load frequency) of the generator already
connected to the system.
Voltage of all generators must be equal.
Synchronizing of Single Phase AC Generator
+ VE
- VE
+ VE - VE
Va
Vb
Vd = Va-Vb
Synchronizing Current
I= Vd/R
Va
Vb
Va
Vb
Va-b
Voltage phase angle of all generators must be equal.
Va
Vb
Va
Vb
Va-Vb
Phase sequence/ rotation of all generators must
be equal.
Phase Sequence
• Phase sequence – R, Y, B
• Phase sequence – A, B, C
Va
Vb
Vb
Va
Va-Vb
Frequency (no load frequency) of the incoming
must be slightly greater than the frequency (no
load frequency) of the generator already
connected to the system.
--------- Incoming Generator
--------------- Running Generator
--------- Incoming Generator
--------------- Running Generator
Method of Synchronization
• Three Dark Lamps Method
• Two Bright, One Dark Method
• Synchroscope Method
Three Dark Lamps Method
If lamps go ON and
OFF concurrently,
indicating that the
phase sequence of
alternator-2
matches with bus
bar. On the other
hand, if they ON
and OFF one after
another, it
resembles the
incorrect phase
sequence.
Two Bright, One Dark Method
Slow /fast identification is
possible
• The sequence of becoming bright and dark L1-
L2 – L3 indicates that the incoming generator
frequency is higher than the bus bar frequency.
Hence, the alternator speed has to be reduced
by prime mover control till the flickering rate
is brought down to a small.
• On the other hand, the sequence flickering L1-
L3 – L2 indicates that incoming alternator
frequency is less than that of bus bar.
Synchroscope Method
Synchroscope