Introduction
Introduction
• An averageof one worker is electrocuted on the
job every day
• There are four main types of electrical injuries:
Electrocution (death due to electrical shock)
Electrical shock
Burns
Falls
3.
Electrical Terminology
Electrical Terminology
•Current – the movement of electrical charge
• Resistance – opposition to current flow
• Voltage – a measure of electrical force
• Conductors – substances, such as metals, that
have little resistance to electricity
• Insulators – substances, such as wood, rubber,
glass, and bakelite, that have high resistance to
electricity
• Grounding – a conductive connection to the earth
which acts as a protective measure
4.
Electrical Shock
Electrical Shock
•Received when current passes
through the body
• Severity of the shock depends on:
Path of current through the body
Amount of current flowing
through the body
Length of time the body is in the
circuit
• LOW VOLTAGE DOES NOT
MEAN LOW HAZARD
5.
Dangers of ElectricalShock
Dangers of Electrical Shock
• Currents greater than 75 mA*
can cause ventricular fibrillation
(rapid, ineffective heartbeat)
• Will cause death in a few
minutes unless a defibrillator is
used
• 75 mA is not much current – a
small power drill uses 30 times
as much
* mA = milliampere = 1/1,000 of an ampere
Defibrillator in use
6.
How is anelectrical shock received?
How is an electrical shock received?
• When two wires have different potential differences
(voltages), current will flow if they are connected
together
In most household wiring, the black wires are at
110 volts relative to ground
The white wires are at zero volts because they
are connected to ground
• If you come into contact with an energized (live)
black wire, and you are also in contact with the
white grounded wire, current will pass through your
body and YOU WILL RECEIVE A SHOCK
7.
How is anelectrical shock received?
How is an electrical shock received?
(cont’d)
(cont’d)
• If you are in contact with an energized wire or any
energized electrical component, and also with any
grounded object, YOU WILL RECEIVE A SHOCK
• You can even receive a shock when you are not in
contact with a ground
If you contact both wires of a 240-volt cable,
YOU WILL RECEIVE A SHOCK and possibly
be electrocuted
8.
Electrical Burns
Electrical Burns
•Most common shock-related,
nonfatal injury
• Occurs when you touch
electrical wiring or equipment
that is improperly used or
maintained
• Typically occurs on the hands
• Very serious injury that needs
immediate attention
9.
Falls
Falls
• Electric shockcan also
cause indirect or
secondary injuries
• Workers in elevated
locations who
experience a shock can
fall, resulting in serious
injury or death
10.
Inadequate Wiring Hazards
InadequateWiring Hazards
• A hazard exists when a conductor is
too small to safely carry the current
• Example: using a portable tool with
an extension cord that has a wire too
small for the tool
The tool will draw more current
than the cord can handle, causing
overheating and a possible fire
without tripping the circuit breaker
The circuit breaker could be the
right size for the circuit but not for
the smaller-wire extension cord
Wire Gauge
WIRE
Wire gauge measures
wires ranging in size from
number 36 to 0 American
wire gauge (AWG)
11.
Overload Hazards
Overload Hazards
•If too many devices are
plugged into a circuit, the
current will heat the wires to
a very high temperature,
which may cause a fire
• If the wire insulation melts,
arcing may occur and cause
a fire in the area where the
overload exists, even inside
a wall
12.
Electrical Protective Devices
ElectricalProtective Devices
• These devices shut off electricity flow in the
event of an overload or ground-fault in the circuit
• Include fuses, circuit breakers, and ground-fault
circuit-interrupters (GFCI’s)
• Fuses and circuit breakers are overcurrent
devices
When there is too much current:
Fuses melt
Circuit breakers trip open
13.
Ground-Fault Circuit Interrupter
Ground-FaultCircuit Interrupter
• This device protects you from dangerous
shock
• The GFCI detects a difference in current
between the black and white circuit wires
(This could happen when electrical
equipment is not working correctly,
causing current “leakage” – known as a
ground fault.)
• If a ground fault is detected, the GFCI
can shut off electricity flow in as little as
1/40 of a second, protecting you from a
dangerous shock
14.
Grounding Hazards
Grounding Hazards
•Some of the most frequently violated OSHA
standards
• Metal parts of an electrical wiring system that we
touch (switch plates, ceiling light fixtures, conduit,
etc.) should be at zero volts relative to ground
• Housings of motors, appliances or tools that are
plugged into improperly grounded circuits may
become energized
• If you come into contact with an improperly grounded
electrical device, YOU WILL BE SHOCKED
15.
Overhead Powerline Hazards
OverheadPowerline Hazards
• Most people don’t realize that
overhead powerlines are usually
not insulated
• Powerline workers need special
training and personal protective
equipment (PPE) to work safely
• Do not use metal ladders –
instead, use fiberglass ladders
• Beware of powerlines when you
work with ladders and scaffolding
16.
Some Examples ofOSHA
Some Examples of OSHA
Electrical Requirements . . . .
Electrical Requirements . . . .
17.
Grounding Path
Grounding Path
•The path to ground from
circuits, equipment, and
enclosures must be
permanent and continuous
• Violation shown here is an
extension cord with a
missing grounding prong
18.
Hand-Held Electric Tools
Hand-HeldElectric Tools
• Hand-held electric tools pose a
potential danger because they make
continuous good contact with the hand
• To protect you from shock, burns, and
electrocution, tools must:
Have a three-wire cord with ground
and be plugged into a grounded
receptacle, or
Be double insulated, or
Be powered by a low-voltage
isolation transformer
19.
Guarding of LiveParts
Guarding of Live Parts
• Must guard live parts of electric
equipment operating at 50 volts or
more against accidental contact by:
Approved cabinets/enclosures, or
Location or permanent partitions
making them accessible only to
qualified persons, or
Elevation of 8 ft. or more above
the floor or working surface
• Mark entrances to guarded locations
with conspicuous warning signs
20.
Guarding of LiveParts
Guarding of Live Parts
• Must enclose or guard
electric equipment in
locations where it would be
exposed to physical damage
• Violation shown here is
physical damage to conduit
21.
Cabinets, Boxes, andFittings
Cabinets, Boxes, and Fittings
• Junction boxes, pull boxes
and fittings must have
approved covers
• Unused openings in cabinets,
boxes and fittings must be
closed (no missing knockouts)
• Photo shows violations of
these two requirements
22.
Permissible Uses ofFlexible
Permissible Uses of Flexible
Cords
Cords
Examples
Examples
Pendant, or
Fixture Wiring
Portable lamps,
tools or appliances
Stationary equipment-
to facilitate interchange
23.
Use of FlexibleCords
Use of Flexible Cords
• More Vulnerable than fixed wiring
• Do not use if a proper wiring method can be used instead
• Flexible cords can be damaged by:
Aging
Edges of doors, windows, equipment frames
Staples or fastenings
Abrasion from nearby materials (rocks, the ground,
other machinery)
Activities in the area
• Improper use of flexible cords can cause shocks, burns or
fires.
24.
Prohibited Uses ofFlexible Cords
Prohibited Uses of Flexible Cords
Examples
Examples
Substitute for
fixed wiring
Run through walls,
ceilings, floors,
doors, or windows
Concealed behind
or attached to
building surfaces
25.
Clues that ElectricalHazards Exist
• Tripped circuit breakers or blown fuses
• Warm tools, wires, cords, connections, or junction boxes
• GFCI that shuts off a circuit
• Worn or frayed insulation around wire or connection
26.
Training
Training
• Deenergizing electricequipment before
inspecting or making repairs
• Using electric tools that are in good repair
• Using good judgment when working near
energized lines
• Using appropriate protective equipment
Train employees working with electric equipment
in safe work practices, including:
27.
Summary
Summary
Hazards
• Inadequate wiring
•Exposed electrical parts
• Wires with bad insulation
• Ungrounded electrical
systems and tools
• Overloaded circuits
• Damaged power tools and
equipment
• Using the wrong PPE and
tools
• Overhead powerlines
• All hazards are made worse
in wet conditions
Protective Measures
• Proper grounding
• Using GFCI’s
• Using fuses and circuit
breakers
• Guarding live parts
• Proper use of flexible
cords
• Training
Editor's Notes
#1 This presentation is designed to assist trainers conducting OSHA 10-hour General Industry outreach training for workers. Since workers are the target audience, this presentation emphasizes hazard identification, avoidance, and control – not standards. No attempt has been made to treat the topic exhaustively. It is essential that trainers tailor their presentations to the needs and understanding of their audience.
This presentation is not a substitute for any of the provisions of the Occupational Safety and Health Act of 1970 or for any standards issued by the U.S. Department of Labor. Mention of trade names, commercial products, or organizations does not imply endorsement by the U.S. Department of Labor.
#2 This module addresses OSHA’s General Industry electrical standards contained in 29 CFR 1910 Subpart S. OSHA also has electrical standards for construction and maritime, but recommends that employers in these industries follow the general industry electrical standards whenever possible for hazards that are not addressed by their industry-specific standards.
Suitability of electrical equipment for an identified purpose may be evidenced by listing or labeling by a nationally recognized testing laboratory which makes periodic inspections of equipment production and states that such equipment meets nationally recognized standards or tests to determine safe use in a specified manner.
The Lockout/Tagout (LOTO) standard, 29 CFR 1910.147, is not covered in this presentation. However, you can find information on the Lockout-Tagout Interactive Training Program, under “OSHA Advisors” on the OSHA web site, www.osha.gov.
Electricity is one of the most common causes of fire in homes and workplaces. Explosions have also resulted from electrical sources.
#3 Operating an electric switch is like turning on a water faucet. Behind the faucet or switch there must be a source of water or electricity with something to transport it, and with a force to make it flow. In the case of water, the source is a reservoir or pumping station; the transportation is through pipes; and the force to make it flow is provided by a pump. For electricity, the source is the power generating station; current travels through electric conductors (wires); and the force to make it flow - voltage, measured in volts, is provided by a generator.
Resistance
- Dry skin has a fairly high resistance, but when moist, resistance drops radically, making it a ready conductor.
- Measured in ohms.
Use extra caution when working with electricity when water is present in the environment or on the skin. Pure water is a poor conductor, but small amounts of impurities, such as salt and acid (both are contained in perspiration), make it a ready conductor.
#4 A small current that passes through the trunk of the body (heart and lungs) is capable of causing severe injury or electrocution.
Low voltages can be extremely dangerous because, all other factors being equal, the degree of injury increases the longer the body is in contact with the circuit.
#6 Grounding is a physical connection to the earth, which is at zero volts.
Electricity travels in closed circuits, and its normal route is through a conductor. Electric shock occurs when the body becomes a part of the circuit. Electric shock normally occurs in one of three ways - when an individual is in contact with the ground and contacts:
1. Both wires of an electric circuit, or
2. One wire of an energized circuit and the ground, or
3. A metallic part that has become energized by contact with an energized conductor. The metal parts of electric tools and machines may become energized if there is a break in the insulation of the tool or machine wiring. A worker using these tools and machines is made less vulnerable to electric shock when there is a low-resistance path from the metallic case of the tool or machine to the ground. This is done through the use of an equipment grounding conductor—a low-resistance wire that causes the unwanted current to pass directly to the ground, thereby greatly reducing the amount of current passing through the body of the person in contact with the tool or machine.
#7 Contact with both energized wires of a 240-volt cable will deliver a shock. This type of shock can occur because one live wire may be at +120 volts while the other is at –120 volts during an alternating current cycle, which is a potential difference of 240 volts.
#10 Note that wire-gauge size is inversely related to the diameter of the wire. For example, a No. 12 flexible cord has a larger diameter wire than a No. 14 flexible cord.
#11 If the circuit breakers or fuses are too big (high current rating) for the wires they are supposed to protect, an overload in the circuit will not be detected and the current will not be shut off. A circuit with improper overcurrent protection devices – or one with no overcurrent protection devices at all – is a hazard.
#12 The basic idea of an overcurrent device is to make a weak link in the circuit. In the case of a fuse, the fuse is destroyed before another part of the system is destroyed. In the case of a circuit breaker, a set of contacts opens the circuit. Unlike a fuse, a circuit breaker can be re-used by re-closing the contacts. Fuses and circuit breakers are designed to protect equipment and facilities, and in so doing, they also provide considerable protection against shock in most situations. However, the only electrical protective device whose sole purpose is to protect people is the ground-fault circuit-interrupter.
#13 The GFCI continually matches the amount of current going to an electrical device against the amount of current returning from the device along the electrical path.
Whenever the amount of current going differs from the amount returning by approximately 5 milliamperes, the GFCI interrupts the electric power within as little as 1/40 of a second, protecting you from a dangerous shock.
GFCI’s are able to detect the loss of current resulting from leakage through a person who is beginning to be shocked. If this situation occurs, the GFCI switches off the current in the circuit.
GFCI’s are different from circuit breakers and fuses because they detect leakage currents rather than overloads.
#14 Grounding is a physical connection to the earth, which is at zero volts.
Current flows through a conductor if there is a difference in voltage (electrical force). If metal parts of an electrical wiring system are at zero volts relative to ground, no current will flow if our body completes the circuit between these parts and ground.
Two kinds of grounds are required by the standard:
1. Service or system ground. In this instance, one wire — called the neutral conductor or grounded conductor — is grounded. In an ordinary low-voltage circuit, the white (or gray) wire is grounded at the generator or transformer and again at the service entrance of the building. This type of ground is primarily designed to protect machines, tools, and insulation against damage.
2. For enhanced worker protection, an additional ground, called the equipment ground, must be furnished by providing another path from the tool or machine through which the current can flow to the ground. This additional ground safeguards the electric equipment operator if a malfunction causes the metal frame of the tool to become energized.
#15 Overhead power lines must be deenergized and grounded by the owner or operator of the lines, or other protective measures must be provided before work is started. Protective measures (such as guarding or insulating the lines) must be designed to prevent contact with the lines.
Minimum clearance distances for employees working in the vicinity of overhead power lines are given in 29 CFR 1910.333(c)(3).
PPE may consist of rubber insulating gloves, hoods, sleeves, matting, blankets, line hose, and industrial protective helmets.
#16 Electrical accidents appear to be caused by a combination of three factors:
1. Unsafe equipment and/or installation,
2. Workplaces made unsafe by the environment, and
3. Unsafe work practices.
There are various ways of protecting people from the hazards caused by electricity. These include: insulation, guarding, grounding, electrical protective devices, and safe work practices.
#18 1910.304(f)(5)(v)(C)(3)
Hazards of portable electric tools:
Currents as small as 10 mA can paralyze, or “freeze” muscles
- Person cannot release tool
- Tool is held even more tightly, resulting in longer exposure to shocking current
Power drills use 30 times as much current as what will kill.
Double-insulated equipment must be distinctly marked to indicate that the equipment utilizes an approved system of double insulation. The common marking is:
#22 1910.305(g)(1)(i)
Other examples:
Elevator cables
Wiring of cranes and hoists
Prevention of the transmission of noise or vibration
Appliances where the fastening means and mechanical connections are designed to permit removal for maintenance and repair
Data processing cables approved as part of the data processing system
#26 OSHA’s electrical safety-related work practice requirements are contained in 29 CFR 1910.331-.335.
Deenergizing Electrical Equipment. The accidental or unexpected sudden starting of electrical equipment can cause severe injury or death. Before ANY inspections or repairs are made the current must be turned off at the switch box and the switch padlocked in the OFF position. At the same time, the switch or controls of the machine or other equipment being locked out of service must be securely tagged to show which equipment or circuits are being worked on.
For more information on the Lockout/Tagout (LOTO) standard, 1910.147, see the Lockout/Tagout Interactive Training Program at the osha web site, www.osha.gov and find this reference under “OSHA Advisors”.